1600kVA dry type cast resin transformer for residential power supply
1600kVA Dry Type Cast Resin Transformer Technical Datasheet
Transformer Type
Dry TypeCast Resin Transformer
Manufacture Standard
IEC60076
Rated Capacity(kVA)
1600
Primary Voltage (kV)
11
Secondary Voltage(kV)
0.44
Cooling Way
AN/AF
Vector Group
Dyn11
Temperature rise
125K
Insulation class
H-CLASS
Impedance
6%
Winding Material
Copper/Copper
Insulation media
Resin Casting
Cast resin Dry type transformer is ideal for installation and easy to maintain on account of both HV and LV windings are cast under vacuum, moisture cannot penetrate and therefore, no drying process is required even in humid conditions after long periods of service. The cast resin transformers comply with IEC60076-11.
CONSTRUCTION
CORE The core is manufactured from cold-rolled grain oriented (CRGO) silicon steel. The steel sheets are cut into required dimensions on automated machines thereby ensuring reduced air gap low exciting current and low noise. Each lamination is insulated from each other to ensure a long trouble-free lifetime of the core. Using 45° stepping all leaning lamination way to laminate. So the no-load current are reduced efficiently.
WINDINGS LV winding is manufactured with high quality foil conductor or copper wire and the ampere-turn is balanceable. The additional loss is low and the ability of anti-short is improved. Oil drawings of heat dispersion are scientifically used in the winding and the surface of heat dissipation is increased so the temperature is reduced and the ability of over-load is improved. HV winding is manufactured with high quality copper wire and excellent design structure. It improves the distribution of electric field. With lighting impulse analysis the ability of anti-lighting impulse has been improved.
STANDARD ACCESSORIES Temperature controller Cooling fans IP20-IP54 protective enclosure
TEST REPORTS AVAILABLE C2/E2/E1 test report Aging test report Aseismatic test report ......